| Sign In | Join Free | My carsrow.com |
|
Brand Name : Schneider Electric
Model Number : GV2ME20
Certification : COO & COC
Place of Origin : Germany
MOQ : 1 pc
Price : $500-$555
Payment Terms : T/T,paypal,alipay
Supply Ability : 99+
Delivery Time : 3-5 days
Packaging Details : Brand new and original
Shipping Weight : 1.2KG
Packing Size : 10x 15x 12.1 cm
Condition : Brand new and original
Warranty : One year
Trade Terms : EXW, DAP, FOB, CIF
Express Delivery : DHL, FedEx, UPS
GV2ME20 Schneider Electric TeSys GV2-Circuit breaker-thermal-magnetic - 13...18 A
Product Overview
Model: GV2ME20
Series: TeSys GV2 Deca
Pole number: 3P
Current range: 13-18 A (Adjustable by knob, 0.5A per division on the scale
Power coverage: 7.5kW @ 400V; 10hp @ 480V
Rated voltage: 690 V AC (50/60 Hz)
Breaking capacity: 100 kA @ 400 V (IEC 60947-2)
Tripping characteristics: Thermal magnetic type - Thermal tripping is adjustable from 13 to 18 A, and magnetic tripping is fixed at 11×In (=198 A)
Control method: Green RUN/red STOP push button on the front, with a contact position indicator window
Terminal: EverLink stainless steel pressure plate, screw clamping 1-25mm ², torque 1.7N ·m
Dimensions: 45mm wide × 89mm high × 78.5mm deep
Service life: 100,000 electrical cycles of AC-3 and 3 million mechanical cycles
Certifications: CE, UL, CSA, CCC, EAC, Marine, ATEX, Green Premium RoHS/REACH
Core features
① One-click setting: Continuously adjustable from 13 to 18 A, no need for an external thermal relay, saving 60% of the cabinet space
② High breaking capacity: 100 kA extreme breaking capacity, no need for high breaking capacity fuses downstream
③ Globally applicable: -25... No volume reduction at +60 ℃, 3000 meters above sea level, suitable for ships, plateaus and deserts
④ Quick installation: The 35mm DIN rail can be clamped in one go, with a width of only 45mm, saving 30% of the space inside the cabinet
⑤ Expandable: GVAE signal contacts can be added to the front, and GVAD fault contacts can be installed on the side, with a maximum of 4 layers and 8 contacts
⑥ Safety visibility: The red "Trip" flag still shows the cause of the trip after power failure, making it convenient for troubleshooting
Typical applications
Direct start/reversible start of 7.5kW and below three-phase asynchronous motors
Main protection for pumps, fans, compressors and conveyor belts
Machine tool spindles, injection molding machines, and extruder motor circuits
Data center cooling towers, cold chain cold storage condensing units
New energy storage cabinet air conditioning fans, photovoltaic tracking bracket motorstors
Accessories (Purchase all at once from the same counter)
GVAE11 (1NO+1NC positive signal)
GVAD0110 (1NO+1NC side fault)
GV2AF01 / GV2AF3 (Mechanically interlocked with LC1D contactor)
GV2MC01 (Transparent IP55 housing, for outdoor use/water pumps)
GV2G454 (4P 54mm busbar, up to 12 units connected in parallel
Product details pictures


Related products
| GV2ME07 | GV2ME08 |
| GV2ME10 | GV2ME14 |
| GV2ME16 | GV2ME21 |
| GV2ME22 | GV2ME32 |
| GV2P07 | GV2P08 |
| GV2P10 | GV2P14 |
| GV2P16 | GV2P20 |
| GV2P22 | GV2P32 |
| GV2LE07 | GV2LE08 |
| GV2LE10 | GV2LE14 |
|
|
GV2ME20 Schneider Electric TeSys GV2-Circuit breaker-thermal-magnetic - 13...18 A Images |